Suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switch boards and power stations. Due to the good laying characteristic, this cable can also be installed in difficult in difficult line guide ways. Contact us  Suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switch boards and power stations. Due to the good laying characteristic, this cable can also be installed in difficult in difficult line guide ways. Contact us Optical Fiber Cables,Opgw Fibre Optical Ground Wire,Ground Wires Overhead Conductor Co., Ltd. , http://www.nspowercable.comEuropean Medium Voltage Power Cable: NA2XSY   6/10 kV, 12/20 kV, 18/30 kV
Â
Application
Â
The inner conducting layer between the conductor and the XLPE insulation and the firmly bonded outer conducting layer on the XLPE insulation assures a construction free of partial discharges with high operational reliabilities.
Technical Data
European
During installation up to -5°C/+23°F
Max. +90°C/+194°F
(Short circuit duration up to 5 sec.)
U0/U 6/10 kV, 12/20 kV, 18/30 kV
6/10 kV = max. 12 kV
12/20 kV = max. 24 kV
18/30 kV = max. 36 kV
6/10 kV = 15 kV
12/20 kV = 30 kV
18/30 kV = 45 kV
During installation max. 15x cable Ø
See Technical Information
Code-Designation for Power Cables with PVC or XLPE Insulation
Design
Identification of Design
Explanations
Conductor
N
According to VDE Standard
(No abbreviation for copper conductor)
A
Aluminum conductors
Y
Insulation of thermoplastic Polyvinyl chloride (PVC)
2X
Insulation cross-linked Polyethylene (XLPE)
Concentric Conductor, Shielding
C
Concentric conductors of copper wires and copper tape, helically wounded
CW
Concentric conductors of copper wires in wave conal formation and and copper tape, helically wounded
CE
Concentric conductors of copper wires and copper tape over each individual conductor, helically wounded
Shielding
S
Shielding of copper wires and copper tape, helically wounded
SE
Shielding of copper wires and copper tape over each individual conductor, helically wounded
(F)
Longitudinally water-proof shielding
Armor
B
Armor of steel tape
F
Armor of galvanized flat steel wires
G
Counter helix of galvanized steel tape
Jacket
K
Lead jacket
Outer Jacket
Y
PVC jacket
2Y
PE jacket
Cable for U0/U 0.6/1 kV are additionally designated with
Â
-J
Cables with green-yellow (green-natural) conductor are marked with protective conductor
-O
Cables without green-yellow (green-natural) conductor are marked without protective conductor
Cable Construction
Â
Â
6/10 kV
12/20 kV
18/30 kV
Description & No. Conductors x cross-sec. mm2, Nominal Voltage
Operation Voltage max.
Insul. Thick-ness mm
Jacket Thick-ness mm
Outer
Dia. min.-max.Copper Weight
kg/kmAlu weight kg/km
Weight ca. kg/km
AWG
NA2XSY 6/10kV 1X50 rm/16
12
3.4
2.5
24.0 - 29.0
182.0
145.0
780.0
1
NA2XSY 6/10kV 1X70 rm/16
12
3.4
2.5
26.0 - 31.0
182.0
203.0
875.0
2/0
NA2XSY 6/10kV 1X95 rm/16
12
3.4
2.5
27.0 - 32.0
182.0
276.0
990.0
3/0
NA2XSY 6/10kV 1X120 rm/16
12
3.4
2.5
29.0 - 34.0
182.0
348.0
1110.0
4/0
NA2XSY 6/10kV 1X150 rm/16
12
3.4
2.5
30.0 - 35.0
182.0
435.0
1240.0
300 kcmil
NA2XSY 6/10kV 1X150 rm/25
12
3.4
2.5
30.0 - 35.0
283.0
435.0
1310.0
300 kcmil
NA2XSY 6/10kV 1X185 rm/25
12
3.4
2.5
32.0 - 37.0
283.0
537.0
1460.0
350 kcmil
NA2XSY 6/10kV 1X185 rm/16
12
3.4
2.5
32.0 - 37.0
182.0
537.0
1405.0
350 kcmil
NA2XSY 6/10kV 1X240 rm/25
12
3.4
2.5
34.0 - 39.0
283.0
696.0
1660.0
500 kcmil
NA2XSY 6/10kV 1X240 rm/16
12
3.4
2.5
34.0 - 39.0
182.0
696.0
1615.0
500 kcmil
NA2XSY 6/10kV 1X300 rm/25
12
3.4
2.5
36.0 - 41.0
283.0
870.0
1910.0
600 kcmil
NA2XSY 6/10kV 1X400 rm/35
12
3.4
2.5
40.0 - 45.0
394.0
1160.0
2315.0
750 kcmil
NA2XSY 6/10kV 1X500 rm/35
12
3.4
2.5
43.0 - 48.0
394.0
1450.0
2750.0
1000 kcmil
Â
NA2XSY 12/20kV 1X50 rm/16
24
5.5
2.5
28.0 - 33.0
182.0
145.0
950.0
1
NA2XSY 12/20kV 1X70 rm/16
24
5.5
2.5
30.0 - 35.0
182.0
203.0
1110.0
2/0
NA2XSY 12/20kV 1X95 rm/16
24
5.5
2.5
31.0 - 36.0
182.0
276.0
1220.0
3/0
NA2XSY 12/20kV 1X120 rm/16
24
5.5
2.5
33.0 - 38.0
182.0
348.0
1310.0
4/0
NA2XSY 12/20kV 1X150 rm/16
24
5.5
2.5
34.0 - 39.0
182.0
435.0
1460.0
300 kcmil
NA2XSY 12/20kV 1X150 rm/25
24
5.5
2.5
34.0 - 39.0
283.0
435.0
1520.0
300 kcmil
NA2XSY 12/20kV 1X185 rm/16
24
5.5
2.5
36.0 - 41.0
182.0
537.0
1660.0
350 kcmil
NA2XSY 12/20kV 1X185 rm/25
24
5.5
2.5
36.0 - 41.0
283.0
537.0
1720.0
350 kcmil
NA2XSY 12/20kV 1X240 rm/25
24
5.5
2.5
39.0 - 44.0
283.0
696.0
1910.0
500 kcmil
NA2XSY 12/20kV 1X240 rm/16
24
5.5
2.5
39.0 - 44.0
182.0
696.0
1860.0
500 kcmil
NA2XSY 12/20kV 1X300 rm/25
24
5.5
2.5
41.0 - 46.0
283.0
870.0
2220.0
600 kcmil
NA2XSY 12/20kV 1X400 rm/35
24
5.5
2.5
44.0 - 49.0
394.0
1160.0
2620.0
750 kcmil
NA2XSY 12/20kV 1X500 rm/35
24
5.5
2.5
47.0 - 52.0
394.0
1450.0
3030.0
1000 kcmil
Â
Description & No. Conductors x cross-sec. mm2, Nominal Voltage
Operation Voltage max.
Insul. Thick-ness mm
Jacket Thick-ness mm
Outer
Dia. min.-max.Copper Weight
kg/kmAlu weight kg/km
Weight ca. kg/km
AWG
NA2XSY 18/30kV 1X50 rm/16
36
8.0
2.5
33.0 - 38.0
182.0
145.0
1260.0
1
NA2XSY 18/30kV 1X70 rm/16
36
8.0
2.5
35.0 - 40.0
182.0
203.0
1360.0
2/0
NA2XSY 18/30kV 1X95 rm/16
36
8.0
2.5
36.0 - 41.0
182.0
276.0
1510.0
3/0
NA2XSY 18/30kV 1X120 rm/16
36
8.0
2.5
38.0 - 43.0
182.0
348.0
1610.0
4/0
NA2XSY 18/30kV 1X150 rm/25
36
8.0
2.5
39.0 - 44.0
283.0
435.0
1810.0
300 kcmil
NA2XSY 18/30kV 1X150 rm/16
36
8.0
2.5
39.0 - 44.0
182.0
435.0
1760.0
300 kcmil
NA2XSY 18/30kV 1X185 rm/16
36
8.0
2.5
41.0 - 46.0
182.0
537.0
1960.0
350 kcmil
NA2XSY 18/30kV 1X185 rm/25
36
8.0
2.5
41.0 - 46.0
283.0
537.0
2020.0
350 kcmil
NA2XSY 18/30kV 1X240 rm/25
36
8.0
2.5
43.0 - 48.0
283.0
696.0
2260.0
500 kcmil
NA2XSY 18/30kV 1X240 rm/16
36
8.0
2.5
43.0 - 48.0
182.0
696.0
2210.0
500 kcmil
NA2XSY 18/30kV 1X300 rm/25
36
8.0
2.5
46.0 - 51.0
283.0
870.0
2560.0
600 kcmil
NA2XSY 18/30kV 1X400 rm/35
36
8.0
2.5
49.0 - 54.0
394.0
1160.0
2960.0
750 kcmil
NA2XSY 18/30kV 1X500 rm/35
36
8.0
2.6
52.0 - 57.0
394.0
1450.0
3460.0
1000 kcmil
Â
Packaging&Delivery.
Â
Packaging Details:Wooden drums,steel wooden drums or as your requirement
Delivery Time:Normally within 30 days(detailly depend on the order quantity)
Looking forward to cooperation with you.If you have any question or need our certification and sample.Pls contact me freely.You can talk with me by Email or chat software. Tel:+86 15039132763
 European Medium Voltage Power Cable: NA2XSY   6/10 kV, 12/20 kV, 18/30 kV
Â
Application
Â
The inner conducting layer between the conductor and the XLPE insulation and the firmly bonded outer conducting layer on the XLPE insulation assures a construction free of partial discharges with high operational reliabilities.
Technical Data
European
During installation up to -5°C/+23°F
Max. +90°C/+194°F
(Short circuit duration up to 5 sec.)
U0/U 6/10 kV, 12/20 kV, 18/30 kV
6/10 kV = max. 12 kV
12/20 kV = max. 24 kV
18/30 kV = max. 36 kV
6/10 kV = 15 kV
12/20 kV = 30 kV
18/30 kV = 45 kV
During installation max. 15x cable Ø
See Technical Information
Code-Designation for Power Cables with PVC or XLPE Insulation
Design
Identification of Design
Explanations
Conductor
N
According to VDE Standard
(No abbreviation for copper conductor)
A
Aluminum conductors
Y
Insulation of thermoplastic Polyvinyl chloride (PVC)
2X
Insulation cross-linked Polyethylene (XLPE)
Concentric Conductor, Shielding
C
Concentric conductors of copper wires and copper tape, helically wounded
CW
Concentric conductors of copper wires in wave conal formation and and copper tape, helically wounded
CE
Concentric conductors of copper wires and copper tape over each individual conductor, helically wounded
Shielding
S
Shielding of copper wires and copper tape, helically wounded
SE
Shielding of copper wires and copper tape over each individual conductor, helically wounded
(F)
Longitudinally water-proof shielding
Armor
B
Armor of steel tape
F
Armor of galvanized flat steel wires
G
Counter helix of galvanized steel tape
Jacket
K
Lead jacket
Outer Jacket
Y
PVC jacket
2Y
PE jacket
Cable for U0/U 0.6/1 kV are additionally designated with
Â
-J
Cables with green-yellow (green-natural) conductor are marked with protective conductor
-O
Cables without green-yellow (green-natural) conductor are marked without protective conductor
Cable Construction
Â
Â
6/10 kV
12/20 kV
18/30 kV
Description & No. Conductors x cross-sec. mm2, Nominal Voltage
Operation Voltage max.
Insul. Thick-ness mm
Jacket Thick-ness mm
Outer
Dia. min.-max.Copper Weight
kg/kmAlu weight kg/km
Weight ca. kg/km
AWG
NA2XSY 6/10kV 1X50 rm/16
12
3.4
2.5
24.0 - 29.0
182.0
145.0
780.0
1
NA2XSY 6/10kV 1X70 rm/16
12
3.4
2.5
26.0 - 31.0
182.0
203.0
875.0
2/0
NA2XSY 6/10kV 1X95 rm/16
12
3.4
2.5
27.0 - 32.0
182.0
276.0
990.0
3/0
NA2XSY 6/10kV 1X120 rm/16
12
3.4
2.5
29.0 - 34.0
182.0
348.0
1110.0
4/0
NA2XSY 6/10kV 1X150 rm/16
12
3.4
2.5
30.0 - 35.0
182.0
435.0
1240.0
300 kcmil
NA2XSY 6/10kV 1X150 rm/25
12
3.4
2.5
30.0 - 35.0
283.0
435.0
1310.0
300 kcmil
NA2XSY 6/10kV 1X185 rm/25
12
3.4
2.5
32.0 - 37.0
283.0
537.0
1460.0
350 kcmil
NA2XSY 6/10kV 1X185 rm/16
12
3.4
2.5
32.0 - 37.0
182.0
537.0
1405.0
350 kcmil
NA2XSY 6/10kV 1X240 rm/25
12
3.4
2.5
34.0 - 39.0
283.0
696.0
1660.0
500 kcmil
NA2XSY 6/10kV 1X240 rm/16
12
3.4
2.5
34.0 - 39.0
182.0
696.0
1615.0
500 kcmil
NA2XSY 6/10kV 1X300 rm/25
12
3.4
2.5
36.0 - 41.0
283.0
870.0
1910.0
600 kcmil
NA2XSY 6/10kV 1X400 rm/35
12
3.4
2.5
40.0 - 45.0
394.0
1160.0
2315.0
750 kcmil
NA2XSY 6/10kV 1X500 rm/35
12
3.4
2.5
43.0 - 48.0
394.0
1450.0
2750.0
1000 kcmil
Â
NA2XSY 12/20kV 1X50 rm/16
24
5.5
2.5
28.0 - 33.0
182.0
145.0
950.0
1
NA2XSY 12/20kV 1X70 rm/16
24
5.5
2.5
30.0 - 35.0
182.0
203.0
1110.0
2/0
NA2XSY 12/20kV 1X95 rm/16
24
5.5
2.5
31.0 - 36.0
182.0
276.0
1220.0
3/0
NA2XSY 12/20kV 1X120 rm/16
24
5.5
2.5
33.0 - 38.0
182.0
348.0
1310.0
4/0
NA2XSY 12/20kV 1X150 rm/16
24
5.5
2.5
34.0 - 39.0
182.0
435.0
1460.0
300 kcmil
NA2XSY 12/20kV 1X150 rm/25
24
5.5
2.5
34.0 - 39.0
283.0
435.0
1520.0
300 kcmil
NA2XSY 12/20kV 1X185 rm/16
24
5.5
2.5
36.0 - 41.0
182.0
537.0
1660.0
350 kcmil
NA2XSY 12/20kV 1X185 rm/25
24
5.5
2.5
36.0 - 41.0
283.0
537.0
1720.0
350 kcmil
NA2XSY 12/20kV 1X240 rm/25
24
5.5
2.5
39.0 - 44.0
283.0
696.0
1910.0
500 kcmil
NA2XSY 12/20kV 1X240 rm/16
24
5.5
2.5
39.0 - 44.0
182.0
696.0
1860.0
500 kcmil
NA2XSY 12/20kV 1X300 rm/25
24
5.5
2.5
41.0 - 46.0
283.0
870.0
2220.0
600 kcmil
NA2XSY 12/20kV 1X400 rm/35
24
5.5
2.5
44.0 - 49.0
394.0
1160.0
2620.0
750 kcmil
NA2XSY 12/20kV 1X500 rm/35
24
5.5
2.5
47.0 - 52.0
394.0
1450.0
3030.0
1000 kcmil
Â
Description & No. Conductors x cross-sec. mm2, Nominal Voltage
Operation Voltage max.
Insul. Thick-ness mm
Jacket Thick-ness mm
Outer
Dia. min.-max.Copper Weight
kg/kmAlu weight kg/km
Weight ca. kg/km
AWG
NA2XSY 18/30kV 1X50 rm/16
36
8.0
2.5
33.0 - 38.0
182.0
145.0
1260.0
1
NA2XSY 18/30kV 1X70 rm/16
36
8.0
2.5
35.0 - 40.0
182.0
203.0
1360.0
2/0
NA2XSY 18/30kV 1X95 rm/16
36
8.0
2.5
36.0 - 41.0
182.0
276.0
1510.0
3/0
NA2XSY 18/30kV 1X120 rm/16
36
8.0
2.5
38.0 - 43.0
182.0
348.0
1610.0
4/0
NA2XSY 18/30kV 1X150 rm/25
36
8.0
2.5
39.0 - 44.0
283.0
435.0
1810.0
300 kcmil
NA2XSY 18/30kV 1X150 rm/16
36
8.0
2.5
39.0 - 44.0
182.0
435.0
1760.0
300 kcmil
NA2XSY 18/30kV 1X185 rm/16
36
8.0
2.5
41.0 - 46.0
182.0
537.0
1960.0
350 kcmil
NA2XSY 18/30kV 1X185 rm/25
36
8.0
2.5
41.0 - 46.0
283.0
537.0
2020.0
350 kcmil
NA2XSY 18/30kV 1X240 rm/25
36
8.0
2.5
43.0 - 48.0
283.0
696.0
2260.0
500 kcmil
NA2XSY 18/30kV 1X240 rm/16
36
8.0
2.5
43.0 - 48.0
182.0
696.0
2210.0
500 kcmil
NA2XSY 18/30kV 1X300 rm/25
36
8.0
2.5
46.0 - 51.0
283.0
870.0
2560.0
600 kcmil
NA2XSY 18/30kV 1X400 rm/35
36
8.0
2.5
49.0 - 54.0
394.0
1160.0
2960.0
750 kcmil
NA2XSY 18/30kV 1X500 rm/35
36
8.0
2.6
52.0 - 57.0
394.0
1450.0
3460.0
1000 kcmil
Â
Packaging&Delivery.
Â
Packaging Details:Wooden drums,steel wooden drums or as your requirement
Delivery Time:Normally within 30 days(detailly depend on the order quantity)
Looking forward to cooperation with you.If you have any question or need our certification and sample.Pls contact me freely.You can talk with me by Email or chat software. Tel:+86 15039132763
Â
Model NO.: NA2XSY 6/10kV 12/20kV 18/30kV
Model: YJV
Armour: Non
Conductor Material: Copper/Aluminum
Standard: VDE 0482-332-1-2, DIN En 60332-1-2 / IEC 60332-1
Quality Guarantee: Ten Years
Core: 1core/Three Cores
Insulated Color: as Your Requirement
Sheath Color: Black
Screen: Copper Wires
Manufacture: Yes
Trademark: Hongda
Transport Package: Wooden Drum
Specification: single core Power Cable
Origin: China, Henan
HS Code: 8544492100
Model NO.: NA2XSY 6/10kV 12/20kV 18/30kV
Model: YJV
Armour: Non
Conductor Material: Copper/Aluminum
Standard: VDE 0482-332-1-2, DIN En 60332-1-2 / IEC 60332-1
Quality Guarantee: Ten Years
Core: 1core/Three Cores
Insulated Color: as Your Requirement
Sheath Color: Black
Screen: Copper Wires
Manufacture: Yes
Trademark: Hongda
Transport Package: Wooden Drum
Specification: single core power cable
Origin: China, Henan
HS Code: 8544492100
Nominal Voltage